Omega Engineering Inc.

 


 

DIN Rail Mount Digital Signal Conditioners

    With RS-485 Communications

  • Models Available for Thermocouple, RTD, Process Voltage, Strain, Frequency, Pulse, ac Voltage, and Current
  • Microprocessor-Based Design
  • 1800 V Isolation
  • Up to 16-Bit Measurement Resolution (Model Dependent)
  • RS-485 Communications
DRX-TC
    The DRX Series digital signal conditioners provide a complete sensor-to-computer solution. The intelligent microprocessor-based modules accept a variety of input signals and produce an RS-485 output signal that may be sent to a computer or virtually any other instrument containing a serial port. The modules offer a wealth of features including a diverse range of input types, configurable operation, networkable communications, and electrical isolation. Models are available for most process signals including thermocouples, RTDs, process voltage, process current, strain, frequency, pulse, ac voltage, and ac current measurement. The DRX Series digital conditioners provide an effective, easily implemented means of automated data monitoring for either laboratory or industrial applications.
Common Specifications
Input Power Supply:
10 to 32 Vdc
Output: 2-wire (half duplex) RS-485
Isolation: 1800 V peak
Typical Step Response to 99%: 1 second
Operating Ambient: -5 to 55°C (23 to 131°F)
Storage Temperature Range: -40 to 85°C (-40 to 185°F)
Mounting: 32 and 35 mm DIN rail
Dimensions: 75 H x 22.5 W x 121 mm D (2.95" x 0.89" x 4.77")
 

Input Thermocouple RTD ac Voltage ac Current Process Strain/Bridge Frequency Pulse
Model DRX-TC DRX-RTD DRX-ACV DRX-ACC DRX-PR DRX-ST DRX-FP
Price $343 $343 $370 $370 $377 $411 $343
Input Type Thermocouple temperature sensor RTD temperature sensor
Pt100, 500, 1000 Cu
ac voltage ac current dc millivolt
dc milliamp
dc volt
millivolt NAMUR
Contact closure
low level
open collector
Input Range J, K, T, E,
R, S, B, N, J DIN
thermocouple full range
= 385, 392
Full range of RTD
2, 3 or 4-wire
Full Scale Range:
400 mV to 400 V
Full Scale Range:
10 mA to 5 A
Full Scale Range:
±400 mV to ±10 V
0 to 20 mA
0 to 30 mV
0 to 100 mV
±100 m
Full Scale Range
20k to 200 M pulses;
0 to 50 kHz
Accuracy ±1°C ±0.5°C 0.2% FS 0.2% FS 0.1% FS 0.2% FS 0.01% FS  0.02% FS
Resolution 0.1°C 0.1°C 10 to 14 Bit 10 to 14 Bit 12 to 15 Bit 13 to 15 Bit 15 to 19 Bit
Output Digital on RS-485 Bus Protocol up to 19.2K Baud Rate
Excitation N/A N/A N/A N/A 14 Vdc @
25 mA
10 V @
30 mA
5, 8.2 and 12.5 Vdc
@ 25 mA

 

 


Free Phone: 1-800-826-6342
Telephone: 1-514-856-6928

omega.com

Please E-Mail your comments and suggestions to OMEGA
or call us @ 1-800-826-6342

© Copyright 1999 OMEGA ENGINEERING, INC. ALL RIGHTS RESERVED.